• EN
  • World market leader
  • Sustainability
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      In case of fire, fire protection curtains close wall and ceiling openings. Their construction (roll-down or folding technique) and the use of different fabrics provide for a wide range of applications as well as different protection goals, classifications and time classes. The casing and guide rails of the highly flexible systems blend almost invisibly into the building and allow plenty of scope for sophisticated architecture and open room concepts.

    • Conveyor system closures

      Conveyor system closures

      Various production and logistics processes call for the most diverse types of conveyor systems. If these conveyor lines pass through fire-retardant or fire-resistant walls or ceilings, the openings required for this purpose must be provided with fire protection closures to prevent the spread of fire through the conveyor system or the goods conveyed. In the event of fire, conveyor system closures (CSC for short) must close these openings immediately and automatically. Fire resistance classified according to DIN EN 13501-2 is just as important as the smooth clearance of the closing areas in the event of a fire.

    • Smoke curtains

      Smoke curtains

      A smoke apron is a part of a smoke control system which also includes other components such as natural smoke and heat exhaust ventilators (EN 12101-2) and mechanical smoke and heat exhaust ventilators (EN 12101-3). Smoke aprons restrict the movement of combustion gases within a building in case of fire.

    • Smoke protection curtains

      Smoke protection curtains

      Once closed, smoke protection curtains (SPC) restrict the passage of smoke during the phase of fire formation, so that in the event of a fire, there is enough time to rescue people and animals from the room behind the curtain and to recover material assets without the need for respiratory equipment.

    • Tube sealings

      Tube sealings

      The solution for issues with fire protection dampers in ventilation and air conditioning systems in conveyor processes. Stöbich offers fire protection for pneumatic conveyor lines the closing elements of which are not exposed to the flow of conveyed material. This way, the closing element cannot be damaged or contaminated by abrasive conveyed goods.

    • Control units

      Control units

      Each automatic fire protection system needs a control unit. They are critical to safety, because a failure of this function means that the entire investment into a fire protection sealing has been in vain. Control units coordinate both fire detection and interaction with other control units, such as higher-level building control systems or clearing of the closing area of conveyor system closures.

  • References
  • Theme worlds
  • News
  • Contact
Product -

Fibershield®-I

System: Fibershield® | Series: Fibershield®-I

Product description

In case of alarm self-closing, thermally insulating

fire protection closure of textile construction in vertical installation position and closing direction.

Type

Heat-insulating fire protection closure with textile design

Verification

CE identification pursuant to EN 16034:2014 in conjunction with EN 13241:2003+A2:2016

Closing direction

From top to bottom

Fire resistance

EI1 30 - EI2 120 • tested according to EN 1634-1: 2014-03 • Classified according to EN 13501-2:2016

Smoke protection

Classified according to EN 13501-2:2016

Closing cycles

C • C1 • C2 • tested according to EN 12605 : 2000-08 • Classified according to EN 13501-2:2016

Fire behaviour of textile

B-s1, d0; E-d2 • Tested according to ISO 11925-2 and EN 13823 • Classified according to EN 13501- 1:2018

Environmental conditions

Special environmental conditions are not taken into account (e.g. humidity > 80 %, ambient temperature < 5 °C and > 45 °C, wind loads etc.).

Visible surfaces

coated in RAL, NCS standard colour, stainless steel V2A material A-1.3401

Constructive system design - System drawing

1 Smoke detector 2 Housing 3 Guide rails 4 Attachment bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release


1 Smoke detector 2 Housing 3 Guide rails 4 Attachment bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release

Classification

Size max. [LB x LH] in mm

Wall thickness*

Housing

Guide rail [a (+c) x b]

EI130

7315 x 4950

150 mm

Type A or Type B

Type 1 or Type 3**

EI230

7315 x 4950

150 mm

Type A or Type B

Type 1 or Type 3**

EI160

6600 x 4840

150 mm

Type B

Type 2

EI260

6600 x 4840

150 mm

Type A or Type B

Type 1 or Type 3**

EI190

6000 x 4400

150 mm

Type B

Type 2

EI290

6000 x 4400

150 mm

Type B

Type 1

EI2120

6600 x 4840

175 mm

Type B

Type 2

C2

6600 x 4840

Sa

Joint length 14.5 m
(3-sided without
end strip)

* The wall can be low density (aerated concrete block) or high density (masonry or concrete). ** Type 3 guide rails – maximum size 3000 x 2870 mm

Casing installation options

Wall mounting with cover

Wall mounting suspended ceiling without cover

Wall without housing cover

Guide rails

Standard

Type 1

Type 2

Type 3

References

Product - Tram Depot | Lund, Sweden

Tram Depot | Lund, Sweden

Product - Wood City | Helsinki, Finland

Wood City | Helsinki, Finland

Product - Raimund Theatre | Vienna, Austria

Raimund Theatre | Vienna, Austria

Product - Gut Schönweide | Grebin, Germany

Gut Schönweide | Grebin, Germany