• EN
  • World market leader
  • Sustainability
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      In case of fire, fire protection curtains close wall and ceiling openings. Their construction (roll-down or folding technique) and the use of different fabrics provide for a wide range of applications as well as different protection goals, classifications and time classes. The casing and guide rails of the highly flexible systems blend almost invisibly into the building and allow plenty of scope for sophisticated architecture and open room concepts.

    • Conveyor system closures

      Conveyor system closures

      Various production and logistics processes call for the most diverse types of conveyor systems. If these conveyor lines pass through fire-retardant or fire-resistant walls or ceilings, the openings required for this purpose must be provided with fire protection closures to prevent the spread of fire through the conveyor system or the goods conveyed. In the event of fire, conveyor system closures (CSC for short) must close these openings immediately and automatically. Fire resistance classified according to DIN EN 13501-2 is just as important as the smooth clearance of the closing areas in the event of a fire.

    • Smoke curtains

      Smoke curtains

      A smoke apron is a part of a smoke control system which also includes other components such as natural smoke and heat exhaust ventilators (EN 12101-2) and mechanical smoke and heat exhaust ventilators (EN 12101-3). Smoke aprons restrict the movement of combustion gases within a building in case of fire.

    • Smoke protection curtains

      Smoke protection curtains

      Once closed, smoke protection curtains (SPC) restrict the passage of smoke during the phase of fire formation, so that in the event of a fire, there is enough time to rescue people and animals from the room behind the curtain and to recover material assets without the need for respiratory equipment.

    • Tube sealings

      Tube sealings

      The solution for issues with fire protection dampers in ventilation and air conditioning systems in conveyor processes. Stöbich offers fire protection for pneumatic conveyor lines the closing elements of which are not exposed to the flow of conveyed material. This way, the closing element cannot be damaged or contaminated by abrasive conveyed goods.

    • Control units

      Control units

      Each automatic fire protection system needs a control unit. They are critical to safety, because a failure of this function means that the entire investment into a fire protection sealing has been in vain. Control units coordinate both fire detection and interaction with other control units, such as higher-level building control systems or clearing of the closing area of conveyor system closures.

  • References
  • Theme worlds
  • News
  • Contact
Product - Supercoil

Supercoil

The conventional smoke apron for high demands and large dimensions

Product description

Supercoil is outstanding for its flexibility in the implementation of made-to-measure solutions. The smoke apron consists of one web part up to 50 m in width and features a drop length of 9.5 m. It is designed for high time classes at temperature loads up to 600 0C (D) and 1,100°C (ETK curve - DH). If guide rails are used, the smoke apron ensures that zero smoke escapes over the entire width of the apron. Thanks to the 'Gravigen' drive motor the apron closes without external energy. Supercoil is also suitable as a floor-closing and partition-forming smoke apron and can be equipped with an opening that allows persons to pass. Furthermore, the clever design allows for a combination with the passable Stripecoil smoke apron.

Supercoil

Type

Textile smoke apron

Proof of usability

CE according to DIN EN 12101-1 • UL 1784

Fabric

Protex 600.1 A2 • Protex 1100.1 A2

Verification

0761-CPD-0060

Closing direction

From top to bottom

Closing cycles

1,000 cycles according to DIN EN 12101-1

Classification

DH 120 • D 60 • Classification according to DIN EN 12101-1

Triggering

Approved hold-open system • To be provided on site

Constructive system design - With guide rail

1 Smoke detector 2 Casing 3 side guides 4 Fixing bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release 11 Wicket door (optional)


1 Smoke detector 2 Casing 3 side guides 4 Fixing bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release 11 Wicket door (optional)

Fabric

System width

Drop length

t (mm)

h (mm)

Protex 600.1 A2 / 1100.1 A2

≥ 0.8 m - ≤ 1.6

≤ 3.5 m

190

250

Protex 600.1 A2 / 1100.1 A2

> 1.6 m - ≤ 30 m

≤ 3.5 m

190

200

Protex 600.1 A2 / 1100.1 A2

≥ 1,2 m ≤ 30 m

> 3.5 m - ≤ 6 m

190

250

Protex 1100.1 A2

≥ 2.0 m ≤ 20 m

> 6 m - ≤ 9 m

235

290

Constructive system design - Without guide rail

1 Smoke detector 2 Casing 4 Fixing bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release


1 Smoke detector 2 Casing 4 Fixing bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release

Fabric

System width

Drop length

t (mm)

h (mm)

Protex 600.1 A2 / 1100.1 A2

≥ 0.8 m - ≤ 1.6

≤ 3.5 m

190

250

Protex 600.1 A2 / 1100.1 A2

> 1.6 m - ≤ 50 m

≤ 3.5 m

190

200

Protex 600.1 A2 / 1100.1 A2

≥ 1,2 m ≤ 50 m

> 3.5 m - ≤ 6 m

190

250

Protex 1100.1 A2

≥ 2.0 m - ≤ 50 m

> 6 m - ≤ 9 m

235

290

Closing strips

Standard

Standard

Closing strips - Standard

Type 4,6

Special

Spring-loaded closing strip

 - Spring-loaded closing strip

Type 4,6 F (Special)

Spring-loaded closing strip

 - Spring-loaded closing strip

Type 3,84 F (Special)

Casing installation options

Wall mounting

Ceiling mounting

Suspension mounting

Guide rails

Standard

Type 105 E (embrasure)

Guide rails - Type 105 E (embrasure)

a 105 mm b 74 mm AL ≤ 6 m A ≤ 50 m²

Type 105 E (niche)

Guide rails - Type 105 E (niche)

a 105 mm b 74 mm AL ≤ 6 m A ≤ 50 m²

Type 105 E(Wall)

Guide rails - Type 105 E(Wall)

a 105 mm b 74 mm AL ≤ 6 m A ≤ 50 m²

Type 80 E

Guide rails - Type 80 E

a 80 mm b 74 mm AL ≤ 3,5 m A ≤ 18 m²

Type 160 E

Guide rails - Type 160 E

a 160 mm b 100 mm AL ≤ 9 m A ≤ 120 m²

References

Product - Olympic Swimming Hall, Munich

Olympic Swimming Hall, Munich

Product - Westfield Mall | Leidschendam, Netherlands

Westfield Mall | Leidschendam, Netherlands

Product - Deutsche Bank Park | Frankfurt am Main, Germany

Deutsche Bank Park | Frankfurt am Main, Germany